For dwelling units, in all areas specified in 210.52, all 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles.
All 15- and 20-ampere, 125-volt non-locking receptacles located in damp or wet locations shall be a listed weather-resistant type.
(a) At least one outlet shall be installed in bathrooms within 36 inches of the outside edge of each basin. The receptacle outlet shall be located on a wall or partition that is adjacent to the basin location, no more than 12” below countertop.
(b) At least one outlet in each car space shall be installed in each attached garage, and in each detached garage with electric power. The garage branch circuit shall not supply outlets outside of the garage. Any receptacles installed specifically for electric vehicles shall be supplied by a separate branch circuit having no other outlets. Exception to supply readily accessible exterior receptacles.
(c) At least two outlets shall be installed outdoors, one on the front and one on the back of the dwelling, accessible at grade level. Outdoor outlets installed in wet locations shall have an enclosure that is weatherproof whether the attachment plug cap is inserted and shall be identified as “extra duty”. Balconies, porches, and decks that are attached to the dwelling unit and are accessible from the interior shall have at least one outlet installed within the perimeter of the balcony, porch or deck.
(d) At least one receptacle must be installed in each unfinished portion of the basement. This receptacle is in addition to any receptacles that may be installed for laundry or other specific purposes.
(e) In every kitchen, family room, dining room, living room, parlor, library, den, sun room, bedroom, recreation room or similar room, or area of dwelling units, receptacle outlets shall be installed so that no point along the floor line in any wall space is more than six feet horizontally, measured from an outlet in that space, including any wall space, two feet or more in width, and excluding only that space occupied by sliding panels in exterior walls. The wall space afforded by fixed room dividers, such as freestanding bar-type counters, or railings, shall be included in the six-foot measurement (Generally stated, this means the first receptacle would be placed within 6 feet of the doorway and the next one within 12 feet of the first one and so forth around the room until you reach another doorway or break in the wall, where you would then need a receptacle within 6 feet of that doorway or break). No outlet may be installed over an electric baseboard heater. These measurements are to be made horizontally along the wall at floor line. Separate wall spaces 2 feet wide or more require a receptacle on them.
(f) In kitchens and dining areas, a receptacle outlet shall be installed at each counter space 12" or wider. Countertop receptacles shall be installed so that no point along the wall line is more than 24", measured horizontally from a receptacle outlet in that space. Peninsular countertops and islands 12" or wider shall have at least one receptacle. (This rule is applied similarly to the 6-12-2-foot dimensions in (e) above except that in the kitchen the dimensions are 24-48- 12 inches beginning at each end of the countertop.)
(g) Receptacles installed in the floor must be installed in a listed floor box. These may be purchased as an assembly at most retail electrical supply stores. Receptacles installed in the floor within 18” of the wall may be used in place of wall mounted receptacles.
(h) A receptacle outlet is required in any dwelling unit hallway that is ten feet or more in length.
(i) At least one 15- or 20-ampere, 125-volt GFCI-protected receptacle must be installed at an indoor spa or hot tub location, not closer than six feet from the inside wall of the unit and not more than ten feet away from it. Light fixtures, outlets and ceiling fans over spas and hot tubs shall be a minimum of7'6" above the maximum water level. Outdoors spa or hot tubs have the same requirements as a swimming pool. Check with your local inspector for those requirements.
(j) A 125-volt, 15- or 20- ampere receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. This outlet shall be located on the same level and within 25 feet of the equipment. This includes roof-mounted equipment. A receptacle outlet shall NOT be required for the service of evaporative coolers for one- and two-family dwellings.
(k) Foyers that are not part of a hallway and are larger than 60 sq. ft. shall have receptacles installed in each wall space 3ft. or more in width and unbroken by doors, floor-to-ceiling windows, and similar openings.